First, the action principle This series of outdoor AC isolating switch's opening and closing action is basically the same. When the three-stage linkage is performed, the independent single-pole isolating switches that have been installed must be connected by parts such as tie rods.
1. The operation mechanism of the isolating switch is connected to the active stage of the isolating switch through the connecting pipe. The main shaft of the mechanism rotates by 90°, and the insulating strut of the active stage is rotated by 90°. The bevel gear in the base drives the insulating pillar on the other side. The direction is rotated to realize the splitting and closing action, and the active stage is rotated by the inter-pole linkage tube to drive the other two driven poles to maintain the three-phase synchronous action.
2. Grounding switch action principle The main shaft of the three-phase grounding switch is connected by a horizontal connecting pipe through the joint. The handle of the operating mechanism is rotated horizontally by 90° or vertically rotated by 180°, and the connecting pipe is driven to rotate by the connecting rod to realize the grounding switch. Gate action.
3. The transmission box is equipped with a transmission box. When the horizontal installation is carried out, the position of the transmission box can be placed between the two poles as needed, or it can be placed at either end of the three poles. The isolating switch operating mechanism is placed underneath and connected to it with a water gas pipe. When the main shaft of the mechanism rotates, the water gas pipe connected to the transmission case drives one of the post insulators in the disconnector to rotate, and the pair of meshing bevel gears in the base drive the other post insulator to rotate. Thereby ensuring the consistency of the left and right touch and closing actions. The opening and closing angles of the isolating switch are both 90°, and the end position of the dividing and closing states is determined by the mechanical limit device of the isolating switch.
4. When using CSl7-G type hand-operated mechanism action principle with CSl7-G type hand-operated mechanism, use CS17-G4, 5, 6 mechanism to divide and close the isolating switch, and move the mechanism pull rod to In the middle position of the “E” groove, the handle of the mechanism can be rotated and rotated by 180°. After the split and closing are completed, the pull rod is moved from the center of the “E” groove to the “minute” and “closed”. In the slot of the end, when the grounding switch is operated by the CS17-G1, 2, and 3 mechanisms, the operation procedure is the same as that of the operation isolating switch, except that the mechanism handle is operated vertically.
5. Equipped with attached electromagnetic lock CSl7-G type hand-operated mechanism action principle with CSl7-G type hand-operated mechanism with electromagnetic lock, move the mechanism pull rod to the middle position of "E'' groove Then press the button of the electromagnetic lock; at the same time, turn the electromagnetic lock knob clockwise to the limit position, and the lock lever will exit the lock hole, then the mechanism handle can be pulled to perform the split and close operation. At the end of the operation, the lock lever of the electromagnetic lock is automatically reset. Finally, move the lever to the locked position.
6. When the CSl7 type hand-operated mechanism is used with the CSl7 type hand-operated mechanism, the operating mechanism is directly connected to the shaft in the base of any one-pole isolating switch through the water gas pipe and the keyway universal joint. When the splitting and closing operation is performed, the upper handle of the mechanism is first placed in a horizontal position, and then horizontally rotated, and the clockwise direction is closed; the counterclockwise direction is opened. The separation position of the isolating switch is limited by the corresponding position on the operating mechanism and the mechanical limit device of the isolating switch. After the operation is completed, the handle is erected and fastened with a locking ring.
7. The auxiliary switch in the operating mechanism is connected with the main shaft of the mechanism, and the corresponding contact is cut or closed during the splitting and closing operation, and the corresponding split and close signals are issued.
8. The splitting and closing action of the isolating switch and the grounding switch is a three-phase synchronous action through the water gas pipe.
Second, installation and adjustment 1, the installation and adjustment of the isolating switch should meet the following requirements:
(1) When using a manual mechanism, the general physical operator should be able to perform the separate and closing operations independently, and the action is flexible.
(2) The closing synchronism value of the three-phase linkage of the isolating switch is: 35kV is not more than 5mm; 110kV is not more than 9mm.
2. Installation and adjustment of the isolating switch (1) Fix the base of each pole isolating switch on the horizontal foundation according to the installation diagram 10 or Figure 11, and make the three-pole grounding knife shaft into a straight line.
(2) Place the operating mechanism under the rotating main shaft on the side of the active side of the isolating switch. When the main body of the isolating switch and the mechanical isolation switch are in the closing position, the water gas pipe is connected and welded firmly. When the main and driven two insulating pillars are not When synchronizing, the pole between the positive and negative teeth can be adjusted to achieve the synchronization of the split and close. The spherical adjustment link on the base is used to adjust the tightness of the four bolts, and the meshing of the bevel gears in the base must be paid attention to. Move its position to ensure flexible operation. Be careful not to tilt the post insulators to the sides, ie the two post insulators should remain in the same plane. After adjustment, retighten the bolts.
(3) The installation and adjustment of the three-phase linkage of the isolating switch in the same period of time, under the condition that the two terminals are subjected to the normal busbar pulling force, the length of the phase-to-phase connecting rod is adjusted to meet the above requirements.
(4) When the isolating switch is in the closing position, all the contact points on the contact should be in contact. The tightening degree of the M8 screw on the contact is just as the spring washer is flattened and the finger can swing to the best condition.
3. Installation and adjustment of the earthing switch (1) When the grounding switch and the mechanical operating spindle are in the closing position, the water gas pipe is connected and welded firmly.
(2) When the grounding switch is in the closing position, the contact contact position can be adjusted by the position of the grounding moving contact on the conductive tube. When the closing position is correct, tighten the tightening nut.